DISTANCE OF EMPLOYEE, UNINSULATED OBJECT OR INSULATED OBJECT FROM ENERGIZED ELECTRICAL UTILITY LINE OR UTILITY LINE EQUIPMENT | ||
Voltage Phase to Phase | Employee or Uninsulated Object | Insulated Object |
Up to 750V | 600 mm | 150 mm |
750V - 15kV | 900 mm | 300 mm |
16kV - 25kV | 1.2 m | 450 mm |
26kV - 69kV | 1.5 m | 900 mm |
  70kV - 138kV | 1.8 m | 1.2 m |
139kV - 230kV | 2.1 m | 1.5 m |
231kV - 345kV | 3.7 m | 3.0 m |
DISTANCE OF PORTION OF TREE FROM ENERGIZED ELECTRICAL UTILITY LINE OR UTILITY LINE EQUIPMENT | ||||||
Voltage Phase to Phase | Where Employee is Using an Uninsulated Object | Where Employee is Using an Insulated Object without an Insulated Aerial Device | Where Employee is Using an Insulated Object with an Insulated Aerial Device | |||
Up to 750v | Â 300 mm | Up to but not touching | Up to but not touching | |||
 750v - 15kV | 600 mm | 300 mm | Up to but not touching | |||
 16kV - 25kV | 750 mm | 450 mm | Up to but not touching | |||
 26kV - 69kV | 1.5 m | 1.0 m | 750 mm | |||
 70kV - 138kV | 1.8 m | 1.2 m | 900 mm | |||
139kV - 230kV | 2.1 m | 1.8 m | 1.5 m | |||
231kV - 345kV | 3.7 m | 3.4 m | 3.0 m | |||
DISTANCE OF EMPLOYEE, UNINSULATED OBJECT OR INSULATED OBJECT FROM ENERGIZED ELECTRICAL UTILITY LINE OR UTILITY LINE EQUIPMENT | ||
Voltage Phase to Phase | Employee or Uninsulated Object | Insulated Object |
Up to 750V | 600 mm | 150 mm |
750V - 15kV | 900 mm | 300 mm |
16kV - 25kV | 1.2 m | 450 mm |
26kV - 69kV | 1.5 m | 900 mm |
  70kV - 138kV | 1.8 m | 1.2 m |
139kV - 230kV | 2.1 m | 1.5 m |
231kV - 345kV | 3.7 m | 3.0 m |
DISTANCE OF PORTION OF TREE FROM ENERGIZED ELECTRICAL UTILITY LINE OR UTILITY LINE EQUIPMENT | ||||||
Voltage Phase to Phase | Where Employee is Using an Uninsulated Object | Where Employee is Using an Insulated Object without an Insulated Aerial Device | Where Employee is Using an Insulated Object with an Insulated Aerial Device | |||
Up to 750v | Â 300 mm | Up to but not touching | Up to but not touching | |||
 750v - 15kV | 600 mm | 300 mm | Up to but not touching | |||
 16kV - 25kV | 750 mm | 450 mm | Up to but not touching | |||
 26kV - 69kV | 1.5 m | 1.0 m | 750 mm | |||
 70kV - 138kV | 1.8 m | 1.2 m | 900 mm | |||
139kV - 230kV | 2.1 m | 1.8 m | 1.5 m | |||
231kV - 345kV | 3.7 m | 3.4 m | 3.0 m | |||
 | ||
 | ||
 | ||
 | ||
 | ||
 | ||
 | ||
 | ||
 | ||
 | ||
 | ||
 | ||
 | ||
DISTANCE OF EMPLOYEE, UNINSULATED OBJECT OR INSULATED OBJECT FROM ENERGIZED ELECTRICAL UTILITY LINE OR UTILITY LINE EQUIPMENT | ||
Voltage Phase to Phase | Employee or Uninsulated Object | Insulated Object |
Up to 750V | 600 mm | 150 mm |
750V - 15kV | 900 mm | 300 mm |
16kV - 25kV | 1.2 m | 450 mm |
26kV - 69kV | 1.5 m | 900 mm |
  70kV - 138kV | 1.8 m | 1.2 m |
139kV - 230kV | 2.1 m | 1.5 m |
231kV - 345kV | 3.7 m | 3.0 m |
DISTANCE OF PORTION OF TREE FROM ENERGIZED ELECTRICAL UTILITY LINE OR UTILITY LINE EQUIPMENT | ||||||
Voltage Phase to Phase | Where Employee is Using an Uninsulated Object | Where Employee is Using an Insulated Object without an Insulated Aerial Device | Where Employee is Using an Insulated Object with an Insulated Aerial Device | |||
Up to 750v | Â 300 mm | Up to but not touching | Up to but not touching | |||
 750v - 15kV | 600 mm | 300 mm | Up to but not touching | |||
 16kV - 25kV | 750 mm | 450 mm | Up to but not touching | |||
 26kV - 69kV | 1.5 m | 1.0 m | 750 mm | |||
 70kV - 138kV | 1.8 m | 1.2 m | 900 mm | |||
139kV - 230kV | 2.1 m | 1.8 m | 1.5 m | |||
231kV - 345kV | 3.7 m | 3.4 m | 3.0 m | |||
 | ||
 | ||
 | ||
 | ||
 | ||
 | ||
 | ||
 | ||
 | ||
 | ||
 | ||
 | ||
 | ||
DISTANCE OF EMPLOYEE, UNINSULATED OBJECT OR INSULATED OBJECT FROM ENERGIZED ELECTRICAL UTILITY LINE OR UTILITY LINE EQUIPMENT | ||
Voltage Phase to Phase | Employee or Uninsulated Object | Insulated Object |
Up to 750V | 600 mm | 150 mm |
750V - 15kV | 900 mm | 300 mm |
16kV - 25kV | 1.2 m | 450 mm |
26kV - 69kV | 1.5 m | 900 mm |
  70kV - 138kV | 1.8 m | 1.2 m |
139kV - 230kV | 2.1 m | 1.5 m |
231kV - 345kV | 3.7 m | 3.0 m |
DISTANCE OF PORTION OF TREE FROM ENERGIZED ELECTRICAL UTILITY LINE OR UTILITY LINE EQUIPMENT | ||||||
Voltage Phase to Phase | Where Employee is Using an Uninsulated Object | Where Employee is Using an Insulated Object without an Insulated Aerial Device | Where Employee is Using an Insulated Object with an Insulated Aerial Device | |||
Up to 750v | Â 300 mm | Up to but not touching | Up to but not touching | |||
 750v - 15kV | 600 mm | 300 mm | Up to but not touching | |||
 16kV - 25kV | 750 mm | 450 mm | Up to but not touching | |||
 26kV - 69kV | 1.5 m | 1.0 m | 750 mm | |||
 70kV - 138kV | 1.8 m | 1.2 m | 900 mm | |||
139kV - 230kV | 2.1 m | 1.8 m | 1.5 m | |||
231kV - 345kV | 3.7 m | 3.4 m | 3.0 m | |||